Smooth, rounded integral bushing in each hub to protect conductor insulation
Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
Allow up to 40% conduit fill in compliance with the National Electrical Code
Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit
Seal must be located within 18 in of either enclosure
Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
Specificationsarrow_drop_down
Application: For minimize the passage of gases and vapors and prevent the passage of flames from one portion of the electrical system to another through the conduit
Country of Origin: MX
Dimensions: 3-11/16 in L x 1-1/4 in W
Finish: Zinc Electroplated
Material: Malleable Iron
Mfg Standards/Approvals: UL 886|UL File No. E34997|CSA C22.2 No. 30|CSA 009795|NEC Articles 500-503/505|Military Specification Mil-F-28675, Class I, Div 1, 2, Groups A, B, C, D, Class I, Zone 1, 2, Groups IIA, IIB, IIC, Class II, Div 1, 2, Groups E, F, G, Class II
Package Height: 0.56 in
Package Length: 6.3 in
Package Weight: 0.94 lb
Package Width: 6.1 in
Series: EYAX
Size: 1/2 in
Suitable For Use With: IMC/Threaded Rigid Metallic Conduit