Products | N3500, Appleton

O-Z/Gedney EYAX-75 Type EYAX Dust-Ignitionproof Explosionproof Horizontal Vertical Conduit Sealing Fitting, 3/4 in

by: Appleton

Locke# N3500 | Mfg# EYAX-75 | UPC# 783126113938
N3500

O-Z/Gedney EYAX-75 Type EYAX Dust-Ignitionproof Explosionproof Horizontal Vertical Conduit Sealing Fitting, 3/4 in

by: Appleton

Locke# N3500 | Mfg# EYAX-75 | UPC# 783126113938

For pricing and availability please Sign In

*Item only available: VA

  • Product Featuresarrow_drop_down
    • To seal vertical or horizontal conduit runs where 40 PCT conductor fill is required
    • To minimize the passage of gases and vapors and prevent the passage of flames from one portion of the electrical system to another through the conduit
    • Use with type EYC sealing compound and type EYF fiber
    • Prevent passage of gases, vapors or flames from one portion of conduit system to another
    • Restrict any explosion to the sealed off enclosure
    • Prevent pressure piling within conduit system
    • Required in class I, division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
    • Required in class I, division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
    • Required in class I, division 1 and 2 locations at the boundary where conduit leaves classified location
    • Required in class I, division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
    • Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, division 2 locations
    • Smooth, rounded integral bushing in each hub to protect conductor insulation
    • Accurately tapped, tapered threads for tight, rigid joints and ground continuity
    • Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
    • Allow up to 40% conduit fill in compliance with the national electrical code
  • Specificationsarrow_drop_down
    • Country of Origin: MX
    • Dimensions: 1-3/4 in Dia x 4-5/16 in L
    • Finish: Electroplated Zinc
    • Material: Malleable Iron
    • Mfg Standards/Approvals: UL File No. E34997|CSA 009795 for Wet Locations|Class I Division 1/2 Group A/B/C/D, Class I Zone 1/2 Group IIA, IIB and IIC, Class II Division 1/2 Group E/F/G, Class III|UL 886|CSA C22.2 No. 30|NEC 500-503/505|Mil-F-28675
    • Package Height: 0.86 in
    • Package Length: 6.8 in
    • Package Weight: 1.85 lb
    • Package Width: 5.2 in
    • Size: 3/4 in
    • Suitable For Use With: IMC/Rigid Metal Conduit
    • Type: Type EYAX Dust-Ignitionproof Explosionproof Horizontal Vertical
    • Warranty: Limited
  • Resourcesarrow_drop_down
  • Tagsarrow_drop_down
Loading
arrow_upward
Feedback